The refrigeration dryer is the most crucial water removal equipment in the post-treatment system of the air compressor. It cools the compressed air to a certain dew point temperature (usually 2 to 10 degrees Celsius), causing the gaseous water vapor in the air to condense into liquid water droplets. Then, through the air-water separator and the automatic drainage valve, these droplets are discharged, thereby obtaining dry compressed air.
- Working pressure: It needs to match the pressure of the air compressor (normal low pressure 0.7-1.0 MPa, medium high pressure requires custom special models).
- Environment and inlet air temperature: For every 5°C increase in temperature, the moisture content in the air and the cooling load will increase significantly. Excessive high environmental temperatures in summer can easily cause the dehumidifier to shut down or result in poor water removal effect.

Flow rate (m³/min): During the selection process, the processing capacity of the dehumidifier must be greater than the actual exhaust volume of the air compressor. It is generally recommended to increase it by 1.2 to 1.5 times to cope with extreme conditions such as high temperatures and high humidity in summer..

Pressure dew point (PDP): The standard pressure dew point of the dehumidifier is usually between 2 and 10°C, corresponding to the atmospheric pressure dew point of approximately -17°C to -23°C. If the process requires a lower dew point (such as -40°C or -70°C), an adsorption dryer (desiccant dryer) should be used in conjunction.
1. By cooling method
- Air-cooled type: Utilizes fan for heat dissipation, easy to install, suitable for small to medium air volume or situations where water source is limited and environmental temperature is low.
- Water-cooled type: Utilizes cooling water for heat dissipation, with stable cooling effect, suitable for systems with large air volume, high environmental temperature or dusty conditions.
2. By intake temperature - Normal temperature type: The intake temperature is generally ≤ 45°C, suitable for systems with a high-efficiency rear cooler at the front end.
- High temperature type: The intake temperature can reach below 80°C, suitable for systems where the exhaust temperature of the air compressor is high and there is no independent cooler.

The four advantages of this integrated design
- Plug-and-play, no installation required: Eliminates the hassle of connecting complex pipelines on-site in traditional post-processing systems, saving time and effort.
- Space-saving: The vertical and compact layout minimizes the floor space, making it ideal for factories or workstations with limited space.
- Low pressure loss: The pipelines have been professionally optimized, with short bends and connection distances, minimizing the pressure drop (pressure loss) of compressed air during the post-processing process.
- Better compatibility: The cold dryer, tank, and filter are pre-matched for flow and pressure at the factory, avoiding "overpowered vehicles pulling small carts" or incomplete water removal issues caused by improper user selection.
.
Disassembly of the core structure of the equipment
1. The deep blue square cabinet on the left: Refrigerated dryer (cold dryer)
- As the first-level water removal core, it is used to cool the compressed air and condense and separate most of the gaseous water and oil mist.
2. The tall blue vertical tank on the right: Air storage tank / Deep adsorption or filtration unit - This tank plays a role in stabilizing the pressure of the pipeline network, buffering the airflow, and further sedimenting moisture in the integrated system. Depending on the design of some laser-cut or high-precision industry integrated machines, some internal parts may also incorporate precision filter cores.
3. Bottom and connecting pipelines: - The entire assembly uses an integrated skid base. The pipelines are already welded and connected at the factory, equipped with a drain valve and pressure gauge. Users can simply connect the main air inlet and outlet on site to put it into use.



Hot Tags: refrigerated compressed air dryer, China refrigerated compressed air dryer manufacturers, suppliers, factory, acre homestead freeze dryer, countertop freeze dryer, freeze dryer laboratory price, freeze dryer lyophilizer price, freezedryers, micro freeze dryer
Technical Parameters
| Model | Treatment air volume |
Air inlet and outlet pipe diameter | Overall dimension mm |
Weight KG |
||
| TKW-1 | 1.6 | G1 | 850 | 565 | 1470 | 180 |
| TKW-2 | 2.6 | DN25 | 910 | 565 | 1510 | 220 |
| TKW-3 | 3.8 | DN40 | 1170 | 565 | 1585 | 310 |
| TKW-6 | 6.5 | DN40 | 1170 | 565 | 2005 | 385 |
| TKW-8 | 8.5 | DN40 | 1220 | 565 | 1850 | 420 |
| TKW-10 | 11.5 | DN50 | 1370 | 620 | 2405 | 670 |
| TKW-12 | 13.5 | DN50 | 1370 | 620 | 2405 | 720 |
| TKW-15 | 17 | DN65 | 1650 | 710 | 2460 | 990 |
| TKW-20 | 20 | DN65 | 1850 | 910 | 2480 | 1020 |
| TKW-25 | 25 | DN65 | 1850 | 810 | 2530 | 1060 |
| TKW-30 | 32 | DN80 | 1820 | 790 | 2575 | 1430 |
| TKW-35 | 38 | DN100 | 2890 | 810 | 2780 | 1470 |
| TKW-40 | 45 | DN100 | 2890 | 810 | 2780 | 1610 |
| TKW-50 | 55 | DN100 | 2130 | 960 | 2770 | 1780 |
| TKW-60 | 65 | DN125 | 2410 | 980 | 3030 | 2020 |
| TKW-70 | 75 | DN125 | 2460 | 1025 | 3050 | 2420 |
| TKW-90 | 90 | DN125 | 2640 | 1130 | 3245 | 2640 |
| TKW-110 | 110 | DN150 | 2710 | 1230 | 3300 | 3335 |
| TKW-130 | 130 | DN150 | 2810 | 1340 | 3350 | 3670 |
| TKW-160 | 160 | DN150 | 2810 | 1340 | 3350 | 4265 |
| TKW-210 | 210 | DN200 | 3810 | 2000 | 3350 | 6400 |
| TKW-260 | 260 | DN200 | 4000 | 2500 | 3350 | 7560 |
| TKW-310 | 310 | DN250 | 5500 | 2800 | 3350 | 10000 |